LC1D38B7
Delivery time:in stock
	
	
		
				 
			
					Range
				 
				
					TeSys 
			
TeSys Deca
				
				 
			
					Range of product
				 
				
					TeSys Deca
				 
			
				 
			
					Product or component type
				 
				
					Contactor
				 
			
				 
			
					Device short name
				 
				
					LC1D
				 
			
				 
			
					Contactor application
				 
				
					Resistive load 
			
Motor control
				
				 
			
					Utilisation category
				 
				
					AC-4 
			
AC-1
AC-3
AC-3e
				
				 
			
					Poles description
				 
				
					3P
				 
			
				 
			
					[Ue] rated operational voltage
				 
				
					Power circuit: <= 690 V AC 25...400 Hz 
			
Power circuit: <= 300 V DC
				
				 
			
					[Ie] rated operational current
				 
				
					50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 
			
38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
				
				 
		
	
					[Uc] control circuit voltage
				 
				
					24 V AC 50/60 Hz
				 
			
		
				 
			
					Motor power kW
				 
				
					18.5 kW at 500 V AC 50/60 Hz (AC-3) 
			
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 380...400 V AC 50/60 Hz (AC-3)
9 kW at 220...230 V AC 50/60 Hz (AC-3)
18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
18.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
9 kW at 220...230 V AC 50/60 Hz (AC-3e)
18.5 kW at 415...440 V AC 50/60 Hz (AC-3e)
				
				 
			
					Motor power hp
				 
				
					10 hp at 230/240 V AC 50/60 Hz for 3 phases motors 
			
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
5 hp at 240 V AC 50/60 Hz for 1 phase motors
20 hp at 480 V AC 50/60 Hz for 3 phases motors
25 hp at 600 V AC 50/60 Hz for 3 phases motors
				
				 
			
					Compatibility code
				 
				
					LC1D
				 
			
				 
			
					Pole contact composition
				 
				
					3 NO
				 
			
				 
			
					Contact compatibility
				 
				
					M2
				 
			
				 
			
					Protective cover
				 
				
					With
				 
			
				 
			
					[Ith] conventional free air thermal current
				 
				
					10 A (at 60 °C) for signalling circuit 
			
50 A (at 60 °C) for power circuit
				
				 
			
					Irms rated making capacity
				 
				
					140 A AC for signalling circuit conforming to IEC 60947-5-1 
			
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
				
				 
			
					Rated breaking capacity
				 
				
					550 A at 440 V for power circuit conforming to IEC 60947
				 
			
				 
			
					[Icw] rated short-time withstand current
				 
				
					60 A 40 °C - 10 min for power circuit 
			
430 A 40 °C - 1 s for power circuit
150 A 40 °C - 1 min for power circuit
310 A 40 °C - 10 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
				
				 
			
					Associated fuse rating
				 
				
					10 A gG for signalling circuit conforming to IEC 60947-5-1 
			
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
				
				 
			
					Average impedance
				 
				
					2 mOhm - Ith 50 A 50 Hz for power circuit
				 
			
				 
			
					Power dissipation per pole
				 
				
					5 W AC-1 
			
3 W AC-3
3 W AC-3e
				
				 
			
					[Ui] rated insulation voltage
				 
				
					Power circuit: 600 V CSA certified 
			
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
				
				 
			
					Overvoltage category
				 
				
					III
				 
			
				 
			
					Pollution degree
				 
				
					3
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					6 kV conforming to IEC 60947
				 
			
				 
			
					Safety reliability level
				 
				
					B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 
			
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
				
				 
			
					Mechanical durability
				 
				
					15 Mcycles
				 
			
				 
			
					Electrical durability
				 
				
					1.4 Mcycles 50 A AC-1 at Ue <= 440 V 
			
1.4 Mcycles 38 A AC-3 at Ue <= 440 V
1.4 Mcycles 38 A AC-3e at Ue <= 440 V
				
				 
			
					Control circuit type
				 
				
					AC at 50/60 Hz
				 
			
				 
			
					Coil technology
				 
				
					Without built-in suppressor module
				 
			
				 
			
					Control circuit voltage limits
				 
				
					0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 
			
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
				
				 
			
					Inrush power in VA
				 
				
					70 VA 60 Hz cos phi 0.75 (at 20 °C) 
			
70 VA 50 Hz cos phi 0.75 (at 20 °C)
				
				 
			
					Hold-in power consumption in VA
				 
				
					7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 
			
7 VA 50 Hz cos phi 0.3 (at 20 °C)
				
				 
			
					Heat dissipation
				 
				
					2…3 W at 50/60 Hz
				 
			
				 
			
					Operating time
				 
				
					4...19 ms opening 
			
12...22 ms closing
				
				 
			
					Maximum operating rate
				 
				
					3600 cyc/h 60 °C
				 
			
				 
			
					Connections - terminals
				 
				
					Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end 
			
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
				
				 
			
					Tightening torque
				 
				
					Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 
			
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
				
				 
			
					Auxiliary contact composition
				 
				
					1 NO + 1 NC
				 
			
				 
			
					Auxiliary contacts type
				 
				
					Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 
			
type mirror contact 1 NC conforming to IEC 60947-4-1
				
				 
			
					Signalling circuit frequency
				 
				
					25...400 Hz
				 
			
				 
			
					Minimum switching voltage
				 
				
					17 V for signalling circuit
				 
			
				 
			
					Minimum switching current
				 
				
					5 mA for signalling circuit
				 
			
				 
			
					Insulation resistance
				 
				
					> 10 MOhm for signalling circuit
				 
			
				 
			
					Non-overlap time
				 
				
					1.5 ms on de-energisation between NC and NO contact 
			
1.5 ms on energisation between NC and NO contact
				
				 
		
	
					Mounting support
				 
				
					Rail 
			
Plate
				
		
				 
			
					Standards
				 
				
					CSA C22.2 No 14 
			
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
				
				 
			
					Product certifications
				 
				
					CSA 
			
LROS (Lloyds register of shipping)
BV
RINA
UL
GOST
DNV
CCC
GL
				
				 
			
					IP degree of protection
				 
				
					IP20 front face conforming to IEC 60529
				 
			
				 
			
					Protective treatment
				 
				
					TH conforming to IEC 60068-2-30
				 
			
				 
			
					Climatic withstand
				 
				
					Conforming to IACS E10 exposure to damp heat 
			
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
				
				 
			
					Permissible ambient air temperature around the device
				 
				
					-40…60 °C 
			
60…70 °C with derating
				
				 
			
					Operating altitude
				 
				
					0...3000 m
				 
			
				 
			
					Fire resistance
				 
				
					850 °C conforming to IEC 60695-2-1
				 
			
				 
			
					Flame retardance
				 
				
					V1 conforming to UL 94
				 
			
				 
			
					Mechanical robustness
				 
				
					Vibrations contactor open (2 Gn, 5...300 Hz) 
			
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (8 Gn for 11 ms)
				
				 
			
					Height
				 
				
					85 mm
				 
			
				 
			
					Width
				 
				
					45 mm
				 
			
				 
			
					Depth
				 
				
					92 mm
				 
			
				 
		
	
					Net weight
				 
				
					0.38 kg