ZLL(LSH)
LV430880
delivery time:in stock
	
| Range | ComPact | 
|---|---|
| Product name | ComPact NSX | 
| Range of product | ComPact NSX100...250 | 
| Device short name | NSX160F | 
| Product or component type | Circuit breaker | 
| Device application | Distribution | 
| Number of poles | 3P | 
| Protected poles description | 3t | 
| [In] rated current | 160 A at 40 °C | 
| [Ue] rated operational voltage | 690 V AC 50/60 Hz | 
| Network type | AC | 
| Network frequency | 50/60 Hz | 
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 | 
| Utilisation category | Category A | 
| [Icu] rated ultimate short-circuit breaking capacity | 
					10 kA at 600 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2  | 
			
| Performance level | F 36 kA 415 V AC | 
| Trip unit name | Micrologic 5.2 A | 
| Trip unit technology | Electronic | 
| Trip unit protection functions | LSI | 
| control type | Toggle | 
| Circuit breaker mounting mode | Fixed |