HCM(ZQC)
LC1D258F7
Delivery time:8-9 weeks
	
	
		Description
	
		
					
							 
						
								Range of Product
							 
							
								TeSys Deca
							 
						
							 
						
								Product or Component Type
							 
							
								Contactor
							 
						
							 
						
								Device short name
							 
							
								LC1D
							 
						
							 
						
								Contactor application
							 
							
								Resistive load
							 
						
							 
						
								Utilisation category
							 
							
								AC-1 
						
AC-3
AC-3e
AC-4
							
							 
						
								Poles description
							 
							
								4P
							 
						
							 
						
								[Ue] rated operational voltage
							 
							
								Power circuit <= 690 V AC 25...400 Hz
							 
						
							 
						
								[Ie] rated operational current
							 
							
								40 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
							 
						
							 
					
				
								[Uc] control circuit voltage
							 
							
								110 V AC 50/60 Hz
							 
						
					
							 
						
								Compatibility code
							 
							
								LC1D
							 
						
							 
						
								Pole contact composition
							 
							
								2 NO + 2 NC
							 
						
							 
						
								Contact compatibility
							 
							
								M6
							 
						
							 
						
								Protective cover
							 
							
								With
							 
						
							 
						
								[Ith] conventional free air thermal current
							 
							
								10 A 140 °F (60 °C) signalling circuit 
						
40 A 140 °F (60 °C) power circuit
							
							 
						
								Irms rated making capacity
							 
							
								140 A AC signalling circuit IEC 60947-5-1 
						
250 A DC signalling circuit IEC 60947-5-1
450 A 440 V power circuit IEC 60947
							
							 
						
								Rated breaking capacity
							 
							
								450 A 440 V power circuit IEC 60947
							 
						
							 
						
								[Icw] rated short-time withstand current
							 
							
								240 A 104 °F (40 °C) - 10 s power circuit 
						
380 A 104 °F (40 °C) - 1 s power circuit
50 A 104 °F (40 °C) - 10 min power circuit
120 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
							
							 
						
								Associated fuse rating
							 
							
								10 A gG signalling circuit IEC 60947-5-1 
						
63 A gG <= 690 V type 1 power circuit
40 A gG <= 690 V type 2 power circuit
							
							 
						
								Average impedance
							 
							
								2 mOhm - Ith 40 A 50 Hz power circuit
							 
						
							 
						
								Power dissipation per pole
							 
							
								3.2 W AC-1
							 
						
							 
						
								[Ui] rated insulation voltage
							 
							
								Power circuit 690 V IEC 60947-4-1 
						
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
							
							 
						
								Overvoltage category
							 
							
								III
							 
						
							 
						
								Pollution degree
							 
							
								3
							 
						
							 
						
								[Uimp] rated impulse withstand voltage
							 
							
								6 kV IEC 60947
							 
						
							 
						
								Safety reliability level
							 
							
								B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 
						
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
							
							 
						
								Mechanical durability
							 
							
								15 Mcycles
							 
						
							 
						
								Electrical durability
							 
							
								1.4 Mcycles 40 A AC-1 <= 440 V
							 
						
							 
						
								Control circuit type
							 
							
								AC 50/60 Hz
							 
						
							 
						
								Coil technology
							 
							
								Without built-in suppressor module
							 
						
							 
						
								Control circuit voltage limits
							 
							
								0.3...0.6 Uc -40…140 °F (-40…60 °C) drop-out AC 50/60 Hz 
						
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
							
							 
						
								Inrush power in VA
							 
							
								70 VA 60 Hz 0.75 68 °F (20 °C)) 
						
70 VA 50 Hz 0.75 68 °F (20 °C))
							
							 
						
								Hold-in power consumption in VA
							 
							
								7.5 VA 60 Hz 0.3 68 °F (20 °C)) 
						
7 VA 50 Hz 0.3 68 °F (20 °C))
							
							 
						
								Heat dissipation
							 
							
								2…3 W 50/60 Hz
							 
						
							 
						
								Operating time
							 
							
								12...22 ms closing 
						
4...19 ms opening
							
							 
						
								Maximum operating rate
							 
							
								3600 cyc/h 140 °F (60 °C)
							 
						
							 
						
								Connections - terminals
							 
							
								Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end 
						
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…16 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…16 mm²) solid without cable end
							
							 
						
								Tightening torque
							 
							
								Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm 
						
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.93 lbf.in (1.8 N.m) screw clamps terminals flat Ø 6 mm
Power circuit 15.93 lbf.in (1.8 N.m) screw clamps terminals Philips No 2
Power circuit 15.93 lbf.in (1.8 N.m) screw clamp terminals pozidriv No 2
							
							 
						
								Auxiliary contact composition
							 
							
								1 NO + 1 NC
							 
						
							 
						
								Auxiliary contacts type
							 
							
								Mechanically linked 1 NO + 1 NC IEC 60947-5-1 
						
Mirror contact 1 NC IEC 60947-4-1
							
							 
						
								Signalling circuit frequency
							 
							
								25...400 Hz
							 
						
							 
						
								Minimum switching voltage
							 
							
								17 V signalling circuit
							 
						
							 
						
								Minimum switching current
							 
							
								5 mA signalling circuit
							 
						
							 
						
								Insulation resistance
							 
							
								> 10 MOhm signalling circuit
							 
						
							 
						
								Non-overlap time
							 
							
								1.5 ms on de-energisation between NC and NO contact 
						
1.5 ms on energisation between NC and NO contact
							
							 
					
				
								Mounting Support
							 
							
								Rail 
						
Plate
							
					
							 
						
								Standards
							 
							
								EN 60947-4-1 
						
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
							
							 
						
								Product Certifications
							 
							
								UL 
						
CSA
CCC
EAC
UKCA
CB
EU-RO-MR by DNV-GL
							
							 
						
								IP degree of protection
							 
							
								IP20 front face IEC 60529
							 
						
							 
						
								Protective treatment
							 
							
								THIEC 60068-2-30
							 
						
							 
						
								Climatic withstand
							 
							
								IACS E10 exposure to damp heat 
						
IEC 60947-1 Annex Q category D exposure to damp heat
							
							 
						
								Permissible ambient air temperature around the device
							 
							
								-40…140 °F (-40…60 °C) 
						
140…158 °F (60…70 °C) with derating
							
							 
						
								Operating altitude
							 
							
								0...9842.52 ft (0...3000 m)
							 
						
							 
						
								Fire resistance
							 
							
								1562 °F (850 °C) IEC 60695-2-1
							 
						
							 
						
								Flame retardance
							 
							
								V1 conforming to UL 94
							 
						
							 
					
				
								Mechanical robustness
							 
							
								Vibrations contactor open 2 Gn, 5...300 Hz) 
						
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor closed 15 Gn for 11 ms)
Shocks contactor open 8 Gn for 11 ms)
							