ZLL(YL)
LC1D098M7
delivery time:in stock
	
	
	
		
				 
			
					Range of Product
				 
				
					TeSys Deca
				 
			
				 
			
					Product or Component Type
				 
				
					Contactor
				 
			
				 
			
					Device short name
				 
				
					LC1D
				 
			
				 
			
					Contactor application
				 
				
					Resistive load
				 
			
				 
			
					Utilisation category
				 
				
					AC-1 
			
AC-3
AC-3e
AC-4
				
				 
			
					Poles description
				 
				
					4P
				 
			
				 
			
					[Ue] rated operational voltage
				 
				
					Power circuit <= 690 V AC 25...400 Hz 
			
Power circuit <= 250 V DC
				
				 
			
					[Ie] rated operational current
				 
				
					20 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
				 
			
				 
		
	
					[Uc] control circuit voltage
				 
				
					220 V AC 50/60 Hz
				 
			
		
				 
			
					Compatibility code
				 
				
					LC1D
				 
			
				 
			
					Pole contact composition
				 
				
					2 NO + 2 NC
				 
			
				 
			
					Contact compatibility
				 
				
					M6
				 
			
				 
			
					Protective cover
				 
				
					With
				 
			
				 
			
					[Ith] conventional free air thermal current
				 
				
					20 A 140 °F (60 °C) power circuit 
			
10 A 140 °F (60 °C) signalling circuit
				
				 
			
					Irms rated making capacity
				 
				
					250 A 440 V power circuit IEC 60947 
			
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
				
				 
			
					Rated breaking capacity
				 
				
					250 A 440 V power circuit IEC 60947
				 
			
				 
			
					[Icw] rated short-time withstand current
				 
				
					105 A 104 °F (40 °C) - 10 s power circuit 
			
210 A 104 °F (40 °C) - 1 s power circuit
30 A 104 °F (40 °C) - 10 min power circuit
61 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
				
				 
			
					Associated fuse rating
				 
				
					10 A gG signalling circuit IEC 60947-5-1 
			
25 A gG <= 690 V type 1 power circuit
20 A gG <= 690 V type 2 power circuit
				
				 
			
					Average impedance
				 
				
					2.5 mOhm - Ith 25 A 50 Hz power circuit
				 
			
				 
			
					Power dissipation per pole
				 
				
					1.56 W AC-1
				 
			
				 
			
					[Ui] rated insulation voltage
				 
				
					Power circuit 690 V IEC 60947-4-1 
			
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
				
				 
			
					Overvoltage category
				 
				
					III
				 
			
				 
			
					Pollution degree
				 
				
					3
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					6 kV IEC 60947
				 
			
				 
			
					Safety reliability level
				 
				
					B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 
			
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
				
				 
			
					Mechanical durability
				 
				
					15 Mcycles
				 
			
				 
			
					Electrical durability
				 
				
					0.3 Mcycles 20 A AC-1 <= 690 V
				 
			
				 
			
					Control circuit type
				 
				
					AC 50/60 Hz
				 
			
				 
			
					Coil technology
				 
				
					Without built-in suppressor module
				 
			
				 
			
					Control circuit voltage limits
				 
				
					0.3...0.6 Uc -40…140 °F (-40…60 °C) drop-out AC 50/60 Hz 
			
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
				
				 
			
					Inrush power in VA
				 
				
					70 VA 60 Hz 0.75 68 °F (20 °C)) 
			
70 VA 50 Hz 0.75 68 °F (20 °C))
				
				 
			
					Hold-in power consumption in VA
				 
				
					7.5 VA 60 Hz 0.3 68 °F (20 °C)) 
			
7 VA 50 Hz 0.3 68 °F (20 °C))
				
				 
			
					Heat dissipation
				 
				
					2…3 W 50/60 Hz
				 
			
				 
			
					Operating time
				 
				
					12...22 ms closing 
			
4...19 ms opening
				
				 
		
	
					Maximum operating rate
				 
				
					3600 cyc/h 140 °F (60 °C)