ZLL(YMX)
LP1D80008
delivery time:in stock
	
	
	
		
				 
			
					Range
				 
				
					TeSys
				 
			
				 
			
					Range of Product
				 
				
					TeSys Deca
				 
			
				 
			
					Product or Component Type
				 
				
					Contactor
				 
			
				 
			
					Device short name
				 
				
					LP1D
				 
			
				 
			
					Contactor application
				 
				
					Resistive load
				 
			
				 
			
					Utilisation category
				 
				
					AC-1
				 
			
				 
			
					Poles description
				 
				
					4P
				 
			
				 
			
					[Ue] rated operational voltage
				 
				
					Power circuit <= 690 V AC 25...400 Hz
				 
			
				 
			
					[Ie] rated operational current
				 
				
					125 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
				 
			
				 
		
	
					[Uc] control circuit voltage
				 
				
					24 V DC
				 
			
		
				 
			
					Compatibility code
				 
				
					LP1D
				 
			
				 
			
					Pole contact composition
				 
				
					2 NO + 2 NC
				 
			
				 
			
					Contact compatibility
				 
				
					M4
				 
			
				 
			
					Protective cover
				 
				
					Without
				 
			
				 
			
					[Ith] conventional free air thermal current
				 
				
					125 A 140 °F (60 °C) power circuit
				 
			
				 
			
					Irms rated making capacity
				 
				
					1100 A 440 V power circuit IEC 60947
				 
			
				 
			
					Rated breaking capacity
				 
				
					1100 A 440 V power circuit IEC 60947
				 
			
				 
			
					[Icw] rated short-time withstand current
				 
				
					135 A 104 °F (40 °C) - 10 min power circuit 
			
320 A 104 °F (40 °C) - 1 min power circuit
640 A 104 °F (40 °C) - 10 s power circuit
990 A 104 °F (40 °C) - 1 s power circuit
				
				 
			
					Associated fuse rating
				 
				
					200 A gG <= 690 V type 1 power circuit 
			
160 A gG <= 690 V type 2 power circuit
				
				 
			
					Average impedance
				 
				
					0.8 mOhm - Ith 125 A 50 Hz power circuit
				 
			
				 
			
					Power dissipation per pole
				 
				
					12.5 W AC-1
				 
			
				 
			
					[Ui] rated insulation voltage
				 
				
					Power circuit 600 V CSA 
			
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
				
				 
			
					Overvoltage category
				 
				
					III
				 
			
				 
			
					Pollution degree
				 
				
					3
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					8 kV IEC 60947
				 
			
				 
			
					Safety reliability level
				 
				
					B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 
			
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
				
				 
			
					Mechanical durability
				 
				
					10 Mcycles
				 
			
				 
			
					Electrical durability
				 
				
					0.8 Mcycles 125 A AC-1 <= 440 V
				 
			
				 
			
					Control circuit type
				 
				
					DC DC standard
				 
			
				 
			
					Coil technology
				 
				
					Without built-in suppressor module
				 
			
				 
			
					Control circuit voltage limits
				 
				
					0.1...0.3 Uc -40…131 °F (-40…55 °C) drop-out DC 
			
0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC
				
				 
			
					Inrush power in W
				 
				
					22 W 68 °F (20 °C))
				 
			
				 
			
					Hold-in power consumption in W
				 
				
					22 W 68 °F (20 °C)
				 
			
				 
			
					Operating time
				 
				
					6...20 ms opening 
			
20...35 ms closing
				
				 
			
					Time constant
				 
				
					75 ms
				 
			
				 
		
	
					Maximum operating rate
				 
				
					3600 cyc/h 140 °F (60 °C)