HCM
SR3B261JD
Delivery time:10-14 weeks
	
	
		
				 
			
					Range of Product
				 
				
					Zelio Logic
				 
			
				 
		
	
					Product or Component Type
				 
				
					Modular smart relay
				 
			
		
				 
			
					local display
				 
				
					With
				 
			
				 
			
					Number or control scheme lines
				 
				
					0…500 FBD 
			
0…240 ladder
				
				 
			
					Cycle time
				 
				
					6…90 ms
				 
			
				 
			
					Backup time
				 
				
					10 years 77 °F (25 °C)
				 
			
				 
			
					Clock drift
				 
				
					12 min/year 32…131 °F (0…55 °C) 
			
6 s/month 77 °F (25 °C)
				
				 
			
					Checks
				 
				
					Program memory on each power up
				 
			
				 
			
					[Us] rated supply voltage
				 
				
					12 V
				 
			
				 
			
					Supply voltage limits
				 
				
					10.4…14.4 V
				 
			
				 
			
					Maximum supply current
				 
				
					250 mA without extension) 
			
400 mA with extensions)
				
				 
			
					Power dissipation in W
				 
				
					3 W without extension 
			
5 W with extensions
				
				 
			
					Reverse polarity protection
				 
				
					With
				 
			
				 
			
					Discrete input number
				 
				
					16 EN/IEC 61131-2 type 1
				 
			
				 
			
					Discrete input type
				 
				
					Resistive
				 
			
				 
			
					Discrete input voltage
				 
				
					12 V DC
				 
			
				 
			
					Discrete input current
				 
				
					4 mA
				 
			
				 
			
					Counting frequency
				 
				
					1 kHz discrete input
				 
			
				 
			
					Voltage state 1 guaranteed
				 
				
					>= 7 V IB...IG used as discrete input circuit 
			
>= 5.6 V I1...IA and IH...IR discrete input circuit
				
				 
			
					Voltage state 0 guaranteed
				 
				
					<= 3 V IB...IG used as discrete input circuit 
			
<= 2.4 V I1...IA and IH...IR discrete input circuit
				
				 
			
					Current state 1 guaranteed
				 
				
					>= 2 mA I1...IA and IH...IR discrete input circuit) 
			
>= 0.5 mA IB...IG used as discrete input circuit)
				
				 
			
					Current state 0 guaranteed
				 
				
					<= 0.2 mA IB...IG used as discrete input circuit) 
			
<= 0.9 mA I1...IA and IH...IR discrete input circuit)
				
				 
			
					Input compatibility
				 
				
					3-wire proximity sensors PNP discrete input
				 
			
				 
			
					Analogue input number
				 
				
					6
				 
			
				 
			
					Analogue Input Type
				 
				
					Common mode
				 
			
				 
			
					Analogue input range
				 
				
					0...12 V 
			
0...10 V
				
				 
			
					Maximum permissible voltage
				 
				
					14.4 V analogue input circuit
				 
			
				 
			
					Analogue input resolution
				 
				
					8 bits at maximum voltage
				 
			
				 
			
					LSB value
				 
				
					39 mV analogue input circuit
				 
			
				 
			
					Conversion time
				 
				
					Smart relay cycle time analogue input circuit
				 
			
				 
			
					Conversion error
				 
				
					+/- 5 % 77 °F (25 °C) analogue input circuit 
			
+/- 6.2 % 131 °F (55 °C) analogue input circuit
				
				 
			
					Repeat accuracy
				 
				
					+/- 2 % 131 °F (55 °C) analogue input circuit
				 
			
				 
			
					Operating distance
				 
				
					10 m between stations, with screened cable (sensor not isolated) analogue input circuit
				 
			
				 
			
					Input impedance
				 
				
					14 kOhm IB...IG used as analogue input circuit 
			
14 kOhm IB...IG used as discrete input circuit
2.7 kOhm I1...IA and IH...IR discrete input circuit
				
				 
			
					Number of Outputs
				 
				
					10 relay
				 
			
				 
			
					Output voltage limits
				 
				
					24...250 V AC relay output) 
			
5...30 V DC relay output)
				
				 
			
					Contacts type and composition
				 
				
					NO relay output
				 
			
				 
			
					Output thermal current
				 
				
					5 A for 2 outputs relay output 
			
8 A for 8 outputs relay output
				
				 
			
					Electrical durability
				 
				
					AC-12 500000 cycles 230 V, 1.5 A relay output EN/IEC 60947-5-1 
			
AC-15 500000 cycles 230 V, 0.9 A relay output EN/IEC 60947-5-1
DC-12 500000 cycles 24 V, 1.5 A relay output EN/IEC 60947-5-1
DC-13 500000 cycles 24 V, 0.6 A relay output EN/IEC 60947-5-1
				
				 
			
					Switching capacity in mA
				 
				
					>= 10 mA 12 V relay output)
				 
			
				 
			
					Operating rate in Hz
				 
				
					0.1 Hz at Ie)relay output 
			
10 Hz no load)relay output
				
				 
			
					Mechanical durability
				 
				
					10000000 cycles relay output
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					4 kV EN/IEC 60947-1 and EN/IEC 60664-1
				 
			
				 
			
					Clock
				 
				
					With
				 
			
				 
			
					Response time
				 
				
					10 ms from state 0 to state 1)relay output 
			
5 ms from state 1 to state 0)relay output
				
				 
			
					Connections - terminals
				 
				
					Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid 
			
Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
				
				 
			
					Tightening torque
				 
				
					4.43 lbf.in (0.5 N.m)
				 
			
				 
			
					Overvoltage category
				 
				
					III EN/IEC 60664-1
				 
			
				 
		
	
					Net Weight
				 
				
					0.88 lb(US) (0.4 kg)
				 
			
		
				 
			
					Immunity to microbreaks
				 
				
					1 ms repeated 20 times
				 
			
				 
			
					Product Certifications
				 
				
					C-tick 
			
UL
CSA
GL
GOST
				
				 
			
					Standards
				 
				
					EN/IEC 60068-2-6 Fc 
			
EN/IEC 61000-4-12
EN/IEC 61000-4-3
EN/IEC 61000-4-6 level 3
EN/IEC 61000-4-5
EN/IEC 61000-4-11
EN/IEC 61000-4-2 level 3
EN/IEC 60068-2-27 Ea
EN/IEC 61000-4-4 level 3
				
				 
			
					IP degree of protection
				 
				
					IP20 IEC 60529 terminal block) 
			
IP40 IEC 60529 front panel)
				
				 
			
					Environmental characteristic
				 
				
					EMC directive EN/IEC 61000-6-2 
			
EMC directive EN/IEC 61000-6-3
EMC directive EN/IEC 61000-6-4
EMC directive EN/IEC 61131-2 zone B
Low voltage directive EN/IEC 61131-2
				
				 
			
					Disturbance radiated/conducted
				 
				
					Class B EN 55022-11 group 1
				 
			
				 
			
					Pollution degree
				 
				
					2 EN/IEC 61131-2
				 
			
				 
			
					Ambient air temperature for operation
				 
				
					-4…104 °F (-20…40 °C) in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 
			
-4…131 °F (-20…55 °C) IEC 60068-2-1 and IEC 60068-2-2
				
				 
			
					Ambient Air Temperature for Storage
				 
				
					-40…158 °F (-40…70 °C)
				 
			
				 
			
					Operating altitude
				 
				
					6561.68 ft (2000 m)
				 
			
				 
			
					Maximum altitude transport
				 
				
					10000.00 ft (3048 m)
				 
			
				 
		
	
					Relative Humidity
				 
				
					95 % without condensation or dripping water