FL SWITCH 2216  2702904
1
  • FL SWITCH 2216  2702904
2
views: 193

FL SWITCH 2216 2702904

Rate:
0.0000/5

( 0 reviews )

Item NO.: V029642 MOQ: 0
Weight:    1kgs
Package Size:  85*130*119mm
 Price:
$815.50
 Qty:
      $815.50
 Shipping:   Calculate Shipping Cost

HCM

FL SWITCH 2216 2702904

Delivery time:in stock


Dimensional drawing
Width 85 mm
Height 130 mm
Depth 119 mm

General Support by phone or on-site (fee is charged)

Housing material Polycarbonate fiber reinforced

Mounting type DIN rail mounting

Ethernet (RJ45)
Connection method RJ45
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100 Mbps
Transmission physics Copper
Transmission length 100 m (per segment)
Signal LEDs Data receive, link status
No. of channels 16 (RJ45 ports)

Digital
Output name Alarm output

Type Book type
Product type Switch
Product family Managed Switch 2000
MTTF 365.63 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
218.22 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
31.7 Years (SN 29500 standard, temperature 55°C, operating cycle 100%)
Special properties Extended temperature range
Signal delay ≥ 6.5 µs (Store and Forward mode, 10/100 Mbps, depending on the frame size)
Insulation characteristics
Protection class III (VDE 0106)
Degree of pollution 2
Switch functions
Diagnostic functions RMON History
LLDP (Link Layer Discovery Protocol)
SNMP-Traps
N:1-Portmirroring
ACD (Address Conflict Detection)
SysLog
CRC-Surveillance
Basic functions Store-and-forward switch, complies with IEEE 802.3
Signal contact control voltage typ. 24 V DC
PROFINET conformance class Conformance-Class B
PROFINET device function PROFINET device
Fast Startup
Filter functions Quality of Service (8 priority classes)
Class of Service
DiffServ/DSCP
Port-Priorisierung
VLAN (up to 32 VLANs)
IGMP Snooping/Querier (v1/v2)
Auto-Query-Port
Extended Multicast Filtering
IP parameterization DHCP-Client
DHCP Option 82 (Relay Agent)
DHCP server (pool-based, port-based)
BootP
DCP (Discovery and Configuration Protocol)
MAC address table 8k
Management Web-based management (HTTP/HTTPS)
Role-based user management (LDAP, RADIUS)
SNMPv1/v2/v3
Command-line interface (Telnet, SSH)
Redundancy MRP (Media Redundancy Protocol)
RSTP (Rapid Spanning Tree Protocol)
FRD (Fast Ring Detection)
Large Tree Support
LACP (Link Aggregation Control Protocol)
PROFINET S2 system redundancy
Status and diagnostic indicators LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)
Additional functions Transmission of MMS and GOOSE (IEC 61850-8-1)
Transmission of Modbus/TCP
Time synchronization SNTP (Simple Network Time Protocol)
Security functions
Port security MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass
Basic functions Store-and-forward switch, complies with IEEE 802.3

Local diagnostics US1/2 Supply voltage US1, US2 Green LED
FAIL Div. LED red
LINK Link status Green LED
Maximum power dissipation for nominal condition 8.4 W (US = Min, Tamb = Max, DOI = Max)
Test voltage 500 V DC
Test section for one minute 500 V DC
Transmission medium Copper
Supply
Supply voltage (DC) 24 V DC (redundant)
Supply voltage range 12 V DC ... 57 V DC
Power supply connection via COMBICON, max. conductor cross section 1.5 mm²
Residual ripple 3.6 VPP (within the permitted voltage range)
Max. current consumption 1.4 A (US = Min, Tamb = Max, DOI = Max)
Typical current consumption 315 mA (at US = 24 V DC and 25 °C ambient temperature)
Current consumption 315 mA
Function
Signal contact control voltage typ. 24 V DC

Connection method Push-in spring connection
Note on the connection method Use only copper connecting cables providing the permitted temperature range (-40 °C ... 75 °C).
Conductor cross section, rigid 0.25 mm² ... 1.5 mm²
Conductor cross section, flexible 0.25 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 9 mm

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Shock (operation) 30g (EN 60068-2-27)
Vibration (operation) in acc. with IEC 60068-2-6: 5g, 150 Hz
Air pressure (operation) 80 kPa ... 110 kPa up to 2000 m above mean sea level (Without derating)
Air pressure (storage/transport) 79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating)

 
No comment