ZLL(LFL)
LC1D65AP7
delivery time:2-3weeks
	
 
	
 
	
		
				 
			
					Range
				 
				
					TeSys 
			
TeSys Deca 
				
				 
			
					Range of product
				 
				
					TeSys Deca 
				 
			
				 
			
					Product or component type
				 
				
					Contactor 
				 
			
				 
			
					Device short name
				 
				
					LC1D 
				 
			
				 
			
					Contactor application
				 
				
					Resistive load 
			
Motor control 
				
				 
			
					utilisation category
				 
				
					AC-4 
			
AC-1
AC-3
AC-3e 
				
				 
			
					Poles description
				 
				
					3P 
				 
			
				 
			
					[Ue] rated operational voltage
				 
				
					Power circuit: <= 690 V AC 25...400 Hz 
			
Power circuit: <= 300 V DC 
				
				 
			
					[Ie] rated operational current
				 
				
					80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 
			
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit 
				
				 
		
	
					[Uc] control circuit voltage
				 
				
					230 V AC 50/60 Hz 
				 
			
		
				 
			
					Motor power kW
				 
				
					11 kW at 400 V AC 50/60 Hz (AC-4) 
			
18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
30 kW at 380...400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660...690 V AC 50/60 Hz (AC-3)
18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
30 kW at 380...400 V AC 50/60 Hz (AC-3e)
37 kW at 500 V AC 50/60 Hz (AC-3e)
37 kW at 660...690 V AC 50/60 Hz (AC-3e) 
				
				 
			
					Motor power hp
				 
				
					40 hp at 460/480 V AC 50/60 Hz for 3 phases motors 
			
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors 
				
				 
			
					Compatibility code
				 
				
					LC1D 
				 
			
				 
			
					Pole contact composition
				 
				
					3 NO 
				 
			
				 
			
					Contact compatibility
				 
				
					M2 
				 
			
				 
			
					Protective cover
				 
				
					With 
				 
			
				 
			
					[Ith] conventional free air thermal current
				 
				
					10 A (at 60 °C) for signalling circuit 
			
80 A (at 60 °C) for power circuit 
				
				 
			
					Irms rated making capacity
				 
				
					140 A AC for signalling circuit conforming to IEC 60947-5-1 
			
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947 
				
				 
			
					Rated breaking capacity
				 
				
					1000 A at 440 V for power circuit conforming to IEC 60947 
				 
			
				 
			
					[Icw] rated short-time withstand current
				 
				
					520 A 40 °C - 10 s for power circuit 
			
900 A 40 °C - 1 s for power circuit
110 A 40 °C - 10 min for power circuit
260 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit 
				
				 
			
					Associated fuse rating
				 
				
					10 A gG for signalling circuit conforming to IEC 60947-5-1 
			
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit 
				
				 
			
					Average impedance
				 
				
					1.5 mOhm - Ith 80 A 50 Hz for power circuit 
				 
			
				 
			
					Power dissipation per pole
				 
				
					9.6 W AC-1 
			
6.3 W AC-3
6.3 W AC-3e 
				
				 
			
					[Ui] rated insulation voltage
				 
				
					Power circuit: 600 V CSA certified 
			
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1 
				
				 
			
					Overvoltage category
				 
				
					III 
				 
			
				 
			
					Pollution degree
				 
				
					3 
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					6 kV conforming to IEC 60947 
				 
			
				 
			
					Safety reliability level
				 
				
					B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 
			
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 
				
				 
			
					Mechanical durability
				 
				
					6 Mcycles 
				 
			
				 
			
					Electrical durability
				 
				
					1.4 Mcycles 80 A AC-1 at Ue <= 440 V 
			
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V 
				
				 
			
					Control circuit type
				 
				
					AC at 50/60 Hz standard 
				 
			
				 
			
					Coil technology
				 
				
					Without built-in suppressor module 
				 
			
				 
			
					Control circuit voltage limits
				 
				
					0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 
			
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz 
				
				 
			
					Inrush power in VA
				 
				
					140 VA 60 Hz cos phi 0.75 (at 20 °C) 
			
160 VA 50 Hz cos phi 0.75 (at 20 °C) 
				
				 
			
					Hold-in power consumption in VA
				 
				
					13 VA 60 Hz cos phi 0.3 (at 20 °C) 
			
15 VA 50 Hz cos phi 0.3 (at 20 °C) 
				
				 
			
					Heat dissipation
				 
				
					4…5 W at 50/60 Hz 
				 
			
				 
			
					Operating time
				 
				
					4...19 ms opening 
			
12...26 ms closing 
				
				 
		
	
					Maximum operating rate
				 
				
					3600 cyc/h 60 °C