XWY(YL)
ATV930D30N4
delivery time: in stock
	
	
	
| Range of product | Altivar Process ATV900 | 
|---|---|
| Device application | Industrial application | 
| Product or component type | Variable speed drive | 
| Product destination | 
				Asynchronous motors Synchronous motors  | 
		
| Product specific application | Process for industrial | 
| variant | 
				With braking chopper Standard version  | 
		
| Network number of phases | 3 phases | 
| Mounting mode | Wall mount | 
| Communication port protocol | 
				Modbus serial EtherNet/IP Modbus TCP  | 
		
| [Us] rated supply voltage | 380...480 V - 15...10 % | 
| Motor power kW | 
				30.0 kW for normal duty 22.0 kW for heavy duty  | 
		
| Motor power hp | 
				40.0 hp for normal duty 30.0 hp for heavy duty  | 
		
| Continuous output current | 
				61.5 A at 4 kHz for normal duty 46.3 A at 4 kHz for heavy duty  | 
		
| EMC filter | 
				Integrated With EMC plate option  | 
		
| IP degree of protection | IP21 | 
| Degree of protection | UL type 1 | 
| option module | 
				Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for EtherCAT Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A/slot B/slot C: digital and analog I/O extension module Slot A/slot B/slot C: output relay extension module Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module communication module for Ethernet Powerlink  | 
		
| Discrete input logic | 16 preset speeds | 
| Asynchronous motor control profile | 
				Constant torque standard Variable torque standard Optimized torque mode  | 
		
| Synchronous motor control profile | 
				Permanent magnet motor Synchronous reluctance motor  | 
		
| Maximum output frequency | 599 Hz | 
| Switching frequency | 
				2...16 kHz adjustable 4...16 kHz with derating factor  | 
		
| Nominal switching frequency | 4 kHz | 
| Line current | 
				53.3 A at 380 V (normal duty) 40.5 A at 380 V (heavy duty) 45.9 A at 480 V (normal duty) 35.8 A at 480 V (heavy duty)  | 
		
| Apparent power | 
				38.1 kVA at 480 V (normal duty) 29.8 kVA at 480 V (heavy duty)  | 
		
| Maximum transient current | 
				73.8 A during 60 s (normal duty) 69.5 A during 60 s (heavy duty)  | 
		
| Network frequency | 50...60 Hz | 
| Prospective line Isc | 50 kA |