XWY
NS33469
delivery time: 4-6 weeks
	
 
	
 
	
 
	
		
				 
			
					Range
				 
				
					ComPact 
				 
			
				 
			
					Product name
				 
				
					ComPact NS 
				 
			
				 
			
					Range of product
				 
				
					ComPact NS630b...1600 
				 
			
				 
			
					device short name
				 
				
					Compact NS800N 
				 
			
				 
			
					Product or component type
				 
				
					Circuit breaker 
				 
			
				 
			
					Device application
				 
				
					Distribution 
				 
			
				 
			
					Number of poles
				 
				
					4P 
				 
			
				 
			
					Protected poles description
				 
				
					4D 
				 
			
				 
			
					Neutral position
				 
				
					Left 
				 
			
				 
			
					(In) rated current up to 65 °C
				 
				
					800 A at 50 °C 
				 
			
				 
			
					[Ue] rated operational voltage
				 
				
					690 V AC 50/60 Hz 
				 
			
				 
			
					Network type
				 
				
					AC 
				 
			
				 
			
					Network frequency
				 
				
					50/60 Hz 
				 
			
				 
			
					suitability for isolation
				 
				
					Yes conforming to EN/IEC 60947-2 
				 
			
				 
			
					Utilisation category
				 
				
					Category B 
				 
			
				 
			
					[Icu] rated ultimate short-circuit breaking capacity
				 
				
					30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 
			
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 
				
				 
			
					Performance level
				 
				
					N 50 kA 415 V AC 
				 
			
				 
			
					Trip unit name
				 
				
					Micrologic 2.0 
				 
			
				 
			
					Trip unit technology
				 
				
					Electronic 
				 
			
				 
			
					Trip unit protection functions
				 
				
					LI 
				 
			
				 
			
					Control type
				 
				
					Rotary handle 
			
Toggle 
				
				 
		
	
					Circuit breaker mounting mode
				 
				
					Fixed 
				 
			
		
				 
			
					[Ui] rated insulation voltage
				 
				
					800 V AC 50/60 Hz conforming to IEC 60947-2 
				 
			
				 
			
					[Uimp] rated impulse withstand voltage
				 
				
					8 kV conforming to IEC 60947-2 
				 
			
				 
			
					[Ics] rated service short-circuit breaking capacity
				 
				
					30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 
			
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 
				
				 
			
					[Icw] rated short-time withstand current
				 
				
					19.2 kA 1 s conforming to IEC 60947-2 
				 
			
				 
			
					Mechanical durability
				 
				
					10000 cycles 
				 
			
				 
			
					electrical durability
				 
				
					2000 cycles at 690 V In 
			
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2 
				
				 
			
					Power losses
				 
				
					15 W 
				 
			
				 
			
					Mounting support
				 
				
					Backplate 
				 
			
				 
			
					Upside connection
				 
				
					Front 
				 
			
				 
			
					Downside connection
				 
				
					Front 
				 
			
				 
			
					connection pitch
				 
				
					70 mm 
				 
			
				 
			
					protection type
				 
				
					L : for overload protection (long time) 
			
I : for instantaneous short-circuit protection 
				
				 
			
					trip unit rating
				 
				
					800 A at 50 °C 
				 
			
				 
			
					Long-time pick-up adjustment type Ir (thermal protection)
				 
				
					Adjustable 9 settings 
				 
			
				 
			
					[Ir] long-time protection pick-up adjustment range
				 
				
					0.4...1 x In 
				 
			
				 
			
					Long-time protection delay adjustment type tr
				 
				
					Adjustable 9 settings 
				 
			
				 
			
					[tr] long-time protection delay adjustment range
				 
				
					12.5…600 s at 1.5 x Ir 
			
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir 
				
				 
			
					Thermal memory
				 
				
					20 mn 
				 
			
				 
			
					Instantaneous protection pick-up adjustment type Ii
				 
				
					Adjustable 
				 
			
				 
			
					[Ii] instantaneous protection pick-up adjustment range
				 
				
					1.5...10 x Ir 
				 
			
				 
			
					Earth-leakage protection
				 
				
					Without 
				 
			
				 
			
					Neutral protection settings
				 
				
					No protection (3D) 
			
0.5 x Ir (3D + N/2)
1 x Ir (4D) 
				
				 
			
					Zone selective interlocking ZSI
				 
				
					Without 
				 
			
				 
			
					Auxiliary contact composition
				 
				
					1 NO/NC 
				 
			
				 
			
					local signalling
				 
				
					4 LEDs (red) for fault indication 
			
1 LED (yellow) for overload 
				
				 
			
					Width (W)
				 
				
					280 mm 
				 
			
				 
			
					Height (H)
				 
				
					327 mm 
				 
			
				 
			
					Depth (D)
				 
				
					147 mm 
				 
			
				 
		
	
					Net weight
				 
				
					18 kg