EVH6-31.5 Series of Unipolar Vacuum Circuit Breakers for Railway
1
  • EVH6-31.5 Series of Unipolar Vacuum Circuit Breakers for Railway
2
views: 385

EVH6-31.5 Series of Unipolar Vacuum Circuit Breakers for Railway

Rate:
0.0000/5

( 0 reviews )

Item NO.: V021452 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$0.00
 Qty:
      $0.00
 Shipping:   Calculate Shipping Cost
EVH6-31.5 series of special unipolar vacuum circuit breakers for railway are single-phase AC 50Hz, rated voltage 31.5kV indoor unipolar circuit breakers. It is specially used in railway substations and partition kiosks for power supply, protection and control of railway traction system.
Circuit breaker adopts integral layout. Operating mechanism is an independent module with independent model. With this method, the structure becomes simple and compact, the mechanism can be encapsulated separately, and then cooperated with the circuit breaker, which greatly improves the production efficiency and the reliability of the mechanical operation of the circuit breaker. Arc extinguishing chamber and operating mechanism of circuit breaker are arranged in front and back mode, with reasonable structure and small volume.

The energy storage part, transmission part, buffer part, release part and mechanical interlocking of the operating mechanism are all integrated into a whole. Only one output interface is connected with the main circuit. The mechanism composition will be fully considered in the design of the mechanism, so that the arrangement of the driving mechanism is reasonable to ensure the minimum deformation of the components. It is convenient to ensure the performance and improve the reliability of the mechanism.


NO Characteristic Reference Number performance index
1 Rated voltage (KV) 31.5
2 Rated current (A) 2500
3 Rated short circuit breaking current (kA) 31.5
4 Rated short circuit current interruption times (times) 30
5 Rated insulation level (before and after interruption) Rated lightning impulse withstand voltage (KV) Interphase and relative 210
Interruption 210
Rated power frequency withstand voltage (KV 1 min) Interphase and relative 110
Interruption 110
Auxiliary Circuit and Control Circuit 2
6 Rated dynamic stable current(kA  peak) 80
7 Rated thermal stable current(kA  4s) 31.5
8 Rated short circuit closing current(kA  peak) 80
9 Mechanical life(次) 20000

 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com