SCB-1600/11
Promulgator
:admin Time:2020-05-26
|
Transformer:
Model No: SCB-1600/11; Rated Power: 1600KVA; 11kV/0.72kV; 3PHASE, 50Hz; Rated
Current: (Primary Side): 84A; (Secondary Side): 1339A; System earthing: IT
System; Neutral Earthing: Earth fault Current Limited to 5A Through NER; Δ/Υ; 3Cx120mm2 /
6x(1Cx400mm2); Dimension: 2400mm x1650mm x2310mm; IP43 for Indoor; Method of
cooling: AN; 105 deg. C (Class F rise); Vector Group: Dyn11, Class of
insulation: H; Weight: 5350kg;
Manufacturer: Siemens
|
|
Transformer: Model No: SCB-250/0.69; Rated Power: 250KVA;
0.69kV/0.42kV; 3PHASE, 50Hz; Rated Current: (Primary Side): 209A; (Secondary
Side): 361A; System Earthing: TNS System; Neutral Earthing: Solidly
Earth; Δ/Υ; 3C 95mm2 / 4C 185mm2+PE
70mm2; 1600mm x1100mm x 1600mm; IP43
for Indoor; Method of cooling: AN; 105 deg. C (Class F rise); Vector
Group: Dyn11; Class of insulation: H; Weight: 1300kg; Manufacturer: Siemens
|