HCM
XCKJ10513
Delivery time:in stock
MAIN | |
---|---|
Range of product | Telemecanique Limit switches XC Standard |
Series name | Standard format |
Product or component type | Limit switch |
Device short name | XCKJ |
Sensor design | Form A conforming to CENELEC EN 50041 |
Body type | Fixed |
Head type | Rotary head |
Material | Metal |
Body material | Zamak |
Head material | Zamak |
Fixing mode | By the body |
Movement of operating head | Rotary |
Type of operator | Spring return roller lever metal |
Type of approach | Lateral approach, 1 or 2 programmable direction |
Cable entry | 1 entry tapped for Pg 13.5 cable gland, cable outer diameter: 9…12 mm |
Number of poles | 2 |
Contacts type and composition | 1 NC + 1 NO |
Contact operation | Snap action |
COMPLEMENTARY | |
Switch actuation | By 30° cam |
Electrical connection | Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm² |
Contacts insulation form | Zb |
Number of steps | 1 |
Positive opening | With |
Positive opening minimum torque | 0.5 N.m |
Minimum torque for tripping | 0.25 N.m |
Maximum actuation speed | 1.5 m/s |
[Ie] rated operational current |
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A 0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A |
[Ithe] conventional enclosed thermal current | 10 A |
[Ui] rated insulation voltage |
300 V conforming to UL 508 500 V (pollution degree 3) conforming to IEC 60947-1 300 V conforming to CSA C22.2 No 14 |
Maximum resistance across terminals | 25 MOhm conforming to IEC 60255-7 category 3 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60664 6 kV conforming to IEC 60947-1 |
Short-circuit protection | 10 A cartridge fuse, type gG |
Electrical durability |
5000000 cycles, DC-13, inductive load type, 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive load type, 24 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive load type, 48 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
Mechanical durability | 30000000 cycles |
Width | 40 mm |
Height | 77 mm |
Depth | 44 mm |
Net weight | 0.49 kg |
Terminals description ISO n°1 |
(13-14)NO (21-22)NC |
ENVIRONMENT | |
Shock resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
Vibration resistance | 25 gn (f= 10…500 Hz) conforming to IEC 60068-2-6 |
IP degree of protection | IP66 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
Overvoltage category |
Class I conforming to IEC 61140 Class I conforming to NF C 20-030 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…70 °C |
Protective treatment | TH |
Product certifications |
UL CCC CSA |
Standards |
CENELEC EN 50041 EN 60204-1 EN 60947-5-1 CSA C22.2 No 14 IEC 60204-1 UL 508 IEC 60947-5-1 |