ZLL(YMX)
LP1D80008
delivery time:in stock
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LP1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
125 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
[Uc] control circuit voltage
24 V DC
Compatibility code
LP1D
Pole contact composition
2 NO + 2 NC
Contact compatibility
M4
Protective cover
Without
[Ith] conventional free air thermal current
125 A 140 °F (60 °C) power circuit
Irms rated making capacity
1100 A 440 V power circuit IEC 60947
Rated breaking capacity
1100 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
135 A 104 °F (40 °C) - 10 min power circuit
320 A 104 °F (40 °C) - 1 min power circuit
640 A 104 °F (40 °C) - 10 s power circuit
990 A 104 °F (40 °C) - 1 s power circuit
Associated fuse rating
200 A gG <= 690 V type 1 power circuit
160 A gG <= 690 V type 2 power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz power circuit
Power dissipation per pole
12.5 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
0.8 Mcycles 125 A AC-1 <= 440 V
Control circuit type
DC DC standard
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.1...0.3 Uc -40…131 °F (-40…55 °C) drop-out DC
0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC
Inrush power in W
22 W 68 °F (20 °C))
Hold-in power consumption in W
22 W 68 °F (20 °C)
Operating time
6...20 ms opening
20...35 ms closing
Time constant
75 ms
Maximum operating rate
3600 cyc/h 140 °F (60 °C)