HCM
FL SWITCH 2216 2702904
Delivery time:in stock
Dimensional drawing
Width
85 mm
Height
130 mm
Depth
119 mm
General
Support by phone or on-site (fee is charged)
Housing material
Polycarbonate fiber reinforced
Mounting type
DIN rail mounting
Ethernet (RJ45)
Connection method
RJ45
Note on the connection method
Auto negotiation and autocrossing
Transmission speed
10/100 Mbps
Transmission physics
Copper
Transmission length
100 m (per segment)
Signal LEDs
Data receive, link status
No. of channels
16 (RJ45 ports)
Digital
Output name
Alarm output
Type
Book type
Product type
Switch
Product family
Managed Switch 2000
MTTF
365.63 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
218.22 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
31.7 Years (SN 29500 standard, temperature 55°C, operating cycle 100%)
Special properties
Extended temperature range
Signal delay
≥ 6.5 µs (Store and Forward mode, 10/100 Mbps, depending on the frame size)
Insulation characteristics
Protection class
III (VDE 0106)
Degree of pollution
2
Switch functions
Diagnostic functions
RMON History
LLDP (Link Layer Discovery Protocol)
SNMP-Traps
N:1-Portmirroring
ACD (Address Conflict Detection)
SysLog
CRC-Surveillance
Basic functions
Store-and-forward switch, complies with IEEE 802.3
Signal contact control voltage
typ. 24 V DC
PROFINET conformance class
Conformance-Class B
PROFINET device function
PROFINET device
Fast Startup
Filter functions
Quality of Service (8 priority classes)
Class of Service
DiffServ/DSCP
Port-Priorisierung
VLAN (up to 32 VLANs)
IGMP Snooping/Querier (v1/v2)
Auto-Query-Port
Extended Multicast Filtering
IP parameterization
DHCP-Client
DHCP Option 82 (Relay Agent)
DHCP server (pool-based, port-based)
BootP
DCP (Discovery and Configuration Protocol)
MAC address table
8k
Management
Web-based management (HTTP/HTTPS)
Role-based user management (LDAP, RADIUS)
SNMPv1/v2/v3
Command-line interface (Telnet, SSH)
Redundancy
MRP (Media Redundancy Protocol)
RSTP (Rapid Spanning Tree Protocol)
FRD (Fast Ring Detection)
Large Tree Support
LACP (Link Aggregation Control Protocol)
PROFINET S2 system redundancy
Status and diagnostic indicators
LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)
Additional functions
Transmission of MMS and GOOSE (IEC 61850-8-1)
Transmission of Modbus/TCP
Time synchronization
SNTP (Simple Network Time Protocol)
Security functions
Port security
MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass
Basic functions
Store-and-forward switch, complies with IEEE 802.3
Local diagnostics
US1/2 Supply voltage US1, US2 Green LED
FAIL Div. LED red
LINK Link status Green LED
Maximum power dissipation for nominal condition
8.4 W (US = Min, Tamb = Max, DOI = Max)
Test voltage
500 V DC
Test section
for one minute 500 V DC
Transmission medium
Copper
Supply
Supply voltage (DC)
24 V DC (redundant)
Supply voltage range
12 V DC ... 57 V DC
Power supply connection
via COMBICON, max. conductor cross section 1.5 mm²
Residual ripple
3.6 VPP (within the permitted voltage range)
Max. current consumption
1.4 A (US = Min, Tamb = Max, DOI = Max)
Typical current consumption
315 mA (at US = 24 V DC and 25 °C ambient temperature)
Current consumption
315 mA
Function
Signal contact control voltage
typ. 24 V DC
Connection method
Push-in spring connection
Note on the connection method
Use only copper connecting cables providing the permitted temperature range (-40 °C ... 75 °C).
Conductor cross section, rigid
0.25 mm² ... 1.5 mm²
Conductor cross section, flexible
0.25 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Stripping length
9 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Shock (operation)
30g (EN 60068-2-27)
Vibration (operation)
in acc. with IEC 60068-2-6: 5g, 150 Hz
Air pressure (operation)
80 kPa ... 110 kPa up to 2000 m above mean sea level (Without derating)
Air pressure (storage/transport)
79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating)