HCM(YL)
6SE7223-1BL22-0XA0
Delivery time:2-3 days
Supply voltage Load voltage L+ ● Rated value (DC) 24 V ● permissible range, lower limit (DC) 20.4 V ● permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 160 mA Power loss Power loss, typ. 6 W Digital inputs Number of digital inputs 16 Input voltage ● Type of input voltage DC ● for signal "0" 0 to 5 V ● for signal "1" 15V DC to 30V DC Input current ● for signal "1", typ. 4 mA
Input delay (for rated value of input voltage) for standard inputs — at "0" to "1", max. 4.5 ms Digital outputs Number of digital outputs 16 Short-circuit protection No Limitation of inductive shutdown voltage to L+ (-48 V) Output voltage ● for signal "0", max. 0.1 V ● for signal "1", min. 20 V Output current ● for signal "1" rated value 750 mA Total current of the outputs (per group) all mounting positions — Current per conductor/group, max. 3 A; 3 / 3 / 6 Relay outputs Switching capacity of contacts — with inductive load, max. 0.75 A; each output — on lamp load, max. 5 W — with resistive load, max. 0.75 A; each output Cable length ● shielded, max. 500 m ● unshielded, max. 150 m Encoder Connectable encoders ● 2-wire sensor Yes — permissible quiescent current (2-wire sensor), max. 1 mA Potential separation Potential separation digital inputs ● Potential separation digital inputs Yes; Optocoupler ● between the channels, in groups of 4 Potential separation digital outputs ● Potential separation digital outputs Yes; Optocoupler ● between the channels, in groups of 4; 4 / 4 / 8 Isolation Isolation tested with 500 V AC Connection method Plug-in I/O terminals Yes