HCM
FL NAT 2008
Delivery time:3-4 months
Width | 45 mm |
Height | 130 mm |
Depth | 115 mm |
General | Support by phone or on-site (fee is charged) |
Housing material | Polycarbonate fiber reinforced |
Mounting type | DIN rail mounting |
Ethernet (RJ45) | |
Connection method | RJ45 |
Note on the connection method | Auto negotiation and autocrossing |
Transmission speed | 10/100 Mbps |
Transmission physics | Copper |
Transmission length | 100 m (per segment) |
Signal LEDs | Data receive, link status |
No. of channels | 8 (RJ45 ports) |
Type | Book type |
Product type | Switch |
Product family | Managed NAT Switch 2000 |
MTTF | 507.8 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
246.55 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
56.66 Years (SN 29500 standard, temperature 55°C, operating cycle 100%) | |
Special properties | 1:1-NAT, Virtual NAT, IP-Masquerading |
Signal delay | ≥ 6.5 µs (Store and Forward mode, 10/100 Mbps, depending on the frame size) |
Insulation characteristics | |
Protection class | III (VDE 0106) |
Switch functions | |
Diagnostic functions | RMON History |
LLDP (Link Layer Discovery Protocol) | |
SNMP-Traps | |
N:1-Portmirroring | |
ACD (Address Conflict Detection) | |
SysLog | |
CRC-Surveillance | |
Basic functions | Router for standard routing, NAT, 1:1-NAT and port forwarding |
NAT functions | 1:1-NAT |
Virtual-NAT | |
IP-Masquerading | |
Port forwarding | |
PROFINET conformance class | Conformance-Class A |
Filter functions | Quality of Service (8 priority classes) |
Class of Service | |
DiffServ/DSCP | |
Port-Priorisierung | |
VLAN (up to 8 VLANs) | |
IGMP Snooping/Querier (v1/v2) | |
Auto-Query-Port | |
Extended Multicast Filtering | |
IP parameterization | DHCP-Client |
DHCP server (port based) | |
BootP | |
MAC address table | 8k |
Management | Web-based management (HTTP/HTTPS) |
Role-based user management (LDAP, RADIUS) | |
SNMPv1/v2/v3 | |
Command-line interface (Telnet, SSH) | |
Redundancy | MRP (Media Redundancy Protocol) |
RSTP (Rapid Spanning Tree Protocol) | |
Status and diagnostic indicators | LEDs: US (power supply), 2 LEDs per Ethernet port (Link/Activity and Speed) |
Time synchronization | SNTP (Simple Network Time Protocol) |
Security functions | |
Basic functions | Router for standard routing, NAT, 1:1-NAT and port forwarding |
Local diagnostics | US Supply voltage Green LED |
LNK/ACT Link status Green LED | |
SPD Data transmission speed Green LED | |
Maximum power dissipation for nominal condition | 4.86 W (At US = 18 V DC and 60°C ambient temperature) |
Test voltage | 500 V DC |
Test section | for one minute 500 V DC |
Transmission medium | Copper |
Supply | |
Supply voltage (DC) | 24 V DC (single) |
Supply voltage range | 18 V DC ... 32 V DC |
Power supply connection | via COMBICON, max. conductor cross section 1.5 mm² |
Residual ripple | 3.6 VPP (within the permitted voltage range) |
Max. current consumption | 0.35 A (At US = 18 V DC and 60°C ambient temperature) |
Typical current consumption | 180 mA (at US = 24 V DC and 25 °C ambient temperature) |
Current consumption | 180 mA |
Connection method | Screw connection |
Note on the connection method | Use only copper connecting cables providing the permitted temperature range (-40 °C ... 75 °C). |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 7 mm |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | 0 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Shock (operation) | 30g (EN 60068-2-27) |
Vibration (operation) | 2g, according to IEC 60068-2-6 |
Air pressure (operation) | 86 kPa ... 108 kPa (1500 m above sea level) |
Air pressure (storage/transport) | 86 kPa ... 108 kPa |
Free from substances that could impair the application of coating | Yes |
Conformity/Approvals | |
UL, USA | UL 61010-1, Ed.3 / UL 61010-2-201, Ed.1 |
UL, Canada | CSA C22.2 NO.61010-2-201:14, Ed.1 / CSA C22.2 NO.61010-1-12, Ed.3 |
Conformance with EMC directives | EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B |
EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A | |
EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A | |
EN 61000-6-2 EN 61000-4-5 (surge) Criterion B | |
EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A | |
EN 61000-6-2 EN 61000-6-4 (interference) Class A | |
EN 61000-6-2 EN 61000-6-4 (conducted interference) Class A | |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 |