HCM
6ES7222-1BH30-0XB0
Delivery time:3 days
【Product parameters】
General information
Product type designation SM 1222, DQ 16x24 VDC/0.5 A
Supply voltage
Allowable range, lower limit (DC) 20.4 V
Allowable range, upper limit (DC) 28.8 V
Input current
From backplane bus DC 5 V, 140 mA maximum
Power loss
Power loss, typical 2.5 W
Digital output
Number of digital outputs 16
● In Component 1
Short-circuit protection No; External presets
Limit of inductive shutdown voltage (L+) -48 V typical
On-off capability at the output
● 0.5 A maximum when resisting load
● Maximum 5 W at lighting load
Output voltage
● Rated (DC) 24 V
● 0.1 V maximum for signal "0"; Comes with a 10 kOhm load
● For signal "1", the minimum value DC 20 V
Output current
● Rating 0.5 A for signal "1"
● Residual current for signal "0", 10 μA maximum
Output delay when resisting a load
● From "0" to "1" with a maximum of 50 μs
● From "1" to "0", maximum 200 μs
Total current at the output (per group)
Horizontal mounting position
— up to 50 °C and 8 A max; The current of each neutral line
Relay output
The on-off capability of the contacts
— 0.5 A maximum with inductive load
— 5 W maximum at lighting load
— 0.5 A maximum when resisting loads
Wire length
● Shielding, maximum 500 m
● Unshielded, maximum 150 m
Alarm/diagnostic/status information
alarm
● Diagnostic alarm Yes
Diagnostic display LED
● For output state Yes
Potentio-isolated
Digital output potential isolation
● Between channels, group the number of points 1
● AC 500 V between channel and backplane bus
Protection class and protection category
Degree of protection IP IP20
Standards, licenses, certificates
CE marking Yes
CSA License Yes
UL Approved Yes
cULus Yes
FM License Yes
RCM (formerly C-TICK) Yes
KC License Yes
Shipbuilding permit Yes
Environmental requirements
In the open air
● Maximum drop 0.3 m; Five, inside the shipping package
Ambient temperature in operation
● Minimum value -20 °C
● Maximum 60 °C
● Horizontal installation, min. -20 °C
● Horizontal installation, max. 60 °C
● Vertical installation, min. -20 °C
● Vertical installation, max. 50 °C
● Permissible temperature change 5°C to 55°C, 3°C/min
Ambient temperature during transport/storage
● Minimum value -40 °C
● Maximum 70 °C
The air pressure meets the requirements of IEC 60068-2-13
● Storage/transportation, minimum value 660 hPa
● Storage/transport, maximum 1 080 hPa
Relative air humidity
● Non-condensing operation at 25 °C, 95 % maximum
Connection Technology / Title
The front plug required is
Machinery/Materials
Housing material (front)
● Plastic Yes
size
Width 45 mm
Height 100 mm
Depth 75 mm